-
Electrical system complete and all circuits made up with grounds tied together using approved mechanical connection.
-
Smoke detectors installed where required and hardwired together on separate circuit (bedrooms, outside sleeping areas, unfinished basements, top of stairs leading to bedrooms, in room adjoining halls 24 inches higher than hall ceiling).
-
Smoke detectors must be 3’ from return air or supply air registers (manufacturer’s requirement).
-
Service panel properly grounded.
-
Approved bushing used where home runs enter back of service panel.
-
Wiring is not in contact with abrasive surfaces, such as truss gusset plates.
-
Wiring proper distance from hot surfaces.
-
Aluminum wiring at lugs has Anti-oxidant.
-
Two wires of different sizes cannot be under the same lug in the service panel unless approved by manufacturer of service panel.
-
Electrical boxes are not overfilled.
-
Wiring sized for intended use.
-
Bathroom receptacles must be separate 20 amp circuits.
-
Outside receptacles cannot be wired off kitchen, laundry or bathrooms circuits.
-
Outdoor boxes must be weatherproof.
-
Provide two 20 amp small appliance circuits to kitchen and dining area.
-
Provide 20 amp circuit to washer receptacle location in laundry.
-
Provide outlet at front and rear of house (2 outside).
-
Receptacles placed per the requirements (every 12 feet, one in hall if over 10 feet in length, all walls over 2 feet must have one).
-
Electrical boxes properly supported.
-
Ground all metal electrical boxes with approved ground screw.
-
All wiring must terminate in an approve box.
-
NM-B (Romex©) must extend ¼” inside the box with 6” of free conductor in the box and 3 inches past the face of the box.
-
Stair ways must have illumination.
-
Pancake boxes cannot be used as a junction box (termination box only).
-
Wiring properly supported within walls (8” from box and every 4’).
-
Fan boxes properly supported and rated for ceiling fans.
-
Electrical wires not bundled for more than 24” (creates heat).
-
Provide approved bushings for wiring entering metal boxes.
-
Bond the metal gas and water lines (if no metallic piping, service panel should be labeled indicating “non-metallic water piping, do not use for ground”).
-
Bond the building if steel framed.
-
Isolate the grounded conductor in the sub-panel and bond the metal enclosure.
-
Install protective plates on all wiring within 1-¼” of the stud face.
-
Seal all unused opening in the outlet box or service panel.
-
Kitchen countertop receptacles properly spaced.
-
Island countertops must have one receptacle.
-
Bathroom receptacles to be within 36” of lavatory.
-
Each lavatory must be served by a separate receptacle or one centered between lavatories not greater than 36” from either lavatory.
-
Provide convenience receptacle within 25 feet of the equipment location and on the same level (if in crawl space, receptacle must be GFCI protected).
-
Provide switch (at access location) and light in attic or crawl space for equipment and separate single receptacle for appliance plug-in if only one appliance at the location.
-
Exits require lighting within 6 feet.
-
Sub panels cannot be located in closets or bathrooms.
-
Disconnect for appliances at appliance location unless service panel visible.
-
Recessed cans rated for insulation cover or screened to prevent insulation from lying on top of cans.
-
All junction boxes must be accessible.